# TBDY 2018 and the 2027 regulation compared

The main differences between the two texts, topic by topic, side by side with article numbers.

| Topic | TBDY 2018 Chapter 10 | 2027 regulation annex | Article |
| --- | --- | --- | --- |
| Design method | ASD (GKT) or LRFD (YDKT) | LRFD (YDKT) | Section 4.2 |
| Minimum yield stress | 235 MPa | 250 MPa; 220 MPa allowed for purlins, façade girts and non-load-bearing studs | Section 2 |
| Wall thickness range | 0.45 to 16 mm | 0.45 to 4 mm | Section 2 |
| DX51D to DX57D | No separate ban | Not used in load-bearing studs | Section 2 |
| Load-bearing stud wall thickness | At least 0.8 mm | At least 0.9 mm | Section 6 |
| Steel-sheet sheathed panel | 10.2.1.1 mentions OSB and plywood | Among High Ductility Level systems | Section 3 |
| Buildings above 10.5 m | No separate ratio | Demand/capacity in studs at most 0.90 | Section 6 |
| Bracing layout | Figure 10.2 example layouts | One continuous member between top and bottom track | Section 6 |
| Circular hole / web | < 0.70 | < 0.40 | Section 10.1 |
| Between holes, centre to centre | At most 600 mm | At least 600 mm | Section 10.1 |
| Galvanizing | Reference to a standard | At least 180 or 275 g/m² according to Annex 1 | Annex 1 |
| Wind lower limit | Not in the text | Basic speed 28 m/s, characteristic load not less than 0.5 kN/m² | Section 4.3 |
| Floor vibration | None | At least 8 Hz, span/depth at most 18 | Section 7.5 |
| If floor openings exceed 3% | Not in the text | Shell element model and load transfer mechanism | Section 7 |
| Temporary stability | No separate heading | Erection sequence and temporary bracing rule | Section 10.2 |
| Checklist | None | Table 10.1, eight headings | Section 10.3 |
| Fire design | None | Shown by test or by calculation | Section 11 |
| Modular and hybrid | None | 14 m limit, 10% rule | Section 12 |

The table is our own comparison of the two texts and shows the main differences. An article that is not listed here has not necessarily stayed the same.